TIL about the 60 second window on hardwired zones
Was troubleshooting a false alarm at a house on Elm Street last week. Kept getting a trouble signal on zone 4 every night around 3 AM. Turns out the homeowner had a freezer compressor kicking on that caused a voltage drop on the wire. My old mentor never told me that hardwired zones have a 60 second delay before they trigger a trouble condition if the voltage fluctuates. Had to read it in the panel manual when I was about to swap out the whole board. Has anyone else run into weird voltage issues on 12v zones like this?
2 comments
Log in to join the discussion
Log In2 Comments
rileyellis9d ago
Actually it's 60 seconds for the trouble to clear not to trigger, the delay happens after the voltage comes back.
6
grant.nina9d ago
Right, the "60 seconds to clear" part is what got me too. That exact same voltage dip thing happened on a job with a walk-in cooler, drove me nuts until I realized the defrost cycle was pulling just enough juice to freak the panel out.
3